• Steam Distribution Headers

 
Shell boilers are made for capacities up to around 27000 kg/h of steam. When loads in excess of this are required, two or more boilers are connected in parallel, with an installation of four or more boilers not being uncommon. The design of the interconnecting steam header is highly important.The aim should be that the pressure drops between each boiler outlet and the header off-take to the plant should be within 0.1 bar. This will minimise carryover and help to prevent overload and lockout of boilers. 

This is also one of the expertise of TFE. Our manufacturing is robust in nature Immediately after the approval of design material  selection is done then it get to inspection stage after that fabrication come in line and inspection stage of IBR approval 